Standard Heating and Cooling Units to Regulate the Temperature of Liquids
Standard Heating and Cooling Units
Heating and cooling units Temperature regulation: compact, air cooled, ready to use
Cooling Units

Aircon Cooling
Liquid Chillers


Deutsch
The combined cooling/heating and the cooling-only units are compact, air-cooled, plug-in units to regulate the temperature of liquids. The units contain a pump and an expansion tank for the liquid circuit. The units are easy to operate and are quickly set up and taken into operation. The liquid circuit can be connected via flexible tubes (up to 8 circuits). The integrated control unit shows the temperature and pressure of the cooling liquid as well as operational data and error messages.
Standard Combined Heating and Cooling Unit The units are typically used for keeping a constant temperature of:
  • Cooling oil,
  • Injection moulding machines,
  • Quenching baths,
  • Hydraulic systems,
  • Deep drawing machines,
  • Laboratory systems,
  • Roller cooling in printing machines, etc.
Combined Cooling and Heating Units

Type SWK
2000 K-H
SWK
4000 K-H
SWK
7000 K-H
SWK
15000 K-H
Dimensions W/D/H 840/790/1280 mm 840/790/ 1480 mm
Weight 185 kg 195 kg 220 kg 270 kg
Cooling capacity 1) 2900 W 5300 W 8100 W 15200 W
Heating power 3700 W
Leaving water temperature range 6..35 °C
Ambient temperature 10..32 °C
Flow rate (liquid) 1.2 .. 4.8 m3/h
max. external pressure 2.1 .. 1.4 bar
Connection for liquid 19 mm
Cooling circuits 4 6 8 8
Refrigerant R404A R404A R407C R407C
Nominal power rating 4000 W 5300 W
Nominal voltage 3 * 400 V, 50 Hz
Fuse rating 16 A
1) Cooling power given for water as coolant,
    Water outlet temperature 10 °C
    Ambient temperature 32 °C

Cooling-Only Units

Type SWK
2000 K
SWK
4000 K
SWK
7000 K
SWK
15000 K
Dimensions W/D/H 840/790/1280 mm 840/790/ 1480 mm
Weight 185 kg 195 kg 220 kg 270 kg
Cooling power 1) 2900 W 5300 W 8100 W 15200 W
Outflow water temperature range 6..15 °C
Ambient temperature 10..32 °C
Flow rate (liquid) 1.2 .. 4.8 m3/h
max. external pressure 2.1 .. 1.4 bar
Connection for liquid 19 mm
Cooling circuits 4 6 8 8
Refrigerant R404A R404A R407C R407C
Nominal power 1600 W 1900 W 2800 W 5300 W
Nominal voltage 3 * 400 V, 50 Hz
Fuse rating 10 A 16 A 16 A 16 A
1) Cooling power given for water as coolant,
    Water outlet temperature 10 °C
    Ambient temperature 32 °C


top Home Products Service Special Offers References Jobs Contact us