The units are typically used for keeping a constant temperature of:
- Cooling oil,
- Injection moulding machines,
- Quenching baths,
- Hydraulic systems,
- Deep drawing machines,
- Laboratory systems,
- Roller cooling in printing machines, etc.
|
|
 |
 |
 |
Combined Cooling and Heating Units
| Type |
SWK 2000 K-H |
SWK 4000 K-H |
SWK 7000 K-H |
SWK 15000 K-H |
| Dimensions W/D/H |
840/790/1280 mm |
840/790/ 1480 mm |
| Weight |
185 kg |
195 kg |
220 kg |
270 kg |
| Cooling capacity 1) |
2900 W |
5300 W |
8100 W |
15200 W |
| Heating power |
3700 W |
| Leaving water temperature range |
6..35 °C |
| Ambient temperature |
10..32 °C |
| Flow rate (liquid) |
1.2 .. 4.8 m3/h |
| max. external pressure |
2.1 .. 1.4 bar |
| Connection for liquid |
19 mm |
| Cooling circuits |
4 |
6 |
8 |
8 |
| Refrigerant |
R404A |
R404A |
R407C |
R407C |
| Nominal power rating |
4000 W |
5300 W |
| Nominal voltage |
3 * 400 V, 50 Hz |
| Fuse rating |
16 A |
1) Cooling power given for water as coolant, Water outlet temperature 10 °C Ambient temperature 32 °C
Cooling-Only Units
| Type |
SWK 2000 K |
SWK 4000 K |
SWK 7000 K |
SWK 15000 K |
| Dimensions W/D/H |
840/790/1280 mm |
840/790/ 1480 mm |
| Weight |
185 kg |
195 kg |
220 kg |
270 kg |
| Cooling power 1) |
2900 W |
5300 W |
8100 W |
15200 W |
| Outflow water temperature range |
6..15 °C |
| Ambient temperature |
10..32 °C |
| Flow rate (liquid) |
1.2 .. 4.8 m3/h |
| max. external pressure |
2.1 .. 1.4 bar |
| Connection for liquid |
19 mm |
| Cooling circuits |
4 |
6 |
8 |
8 |
| Refrigerant |
R404A |
R404A |
R407C |
R407C |
| Nominal power |
1600 W |
1900 W |
2800 W |
5300 W |
| Nominal voltage |
3 * 400 V, 50 Hz |
| Fuse rating |
10 A |
16 A |
16 A |
16 A |
1) Cooling power given for water as coolant, Water outlet temperature 10 °C Ambient temperature 32 °C
|